You Want the Best Geothermal Heat Pump Available
Dealer Locator
|
Case Studies
|
About ECONAR
|
Contact Information
|
Home
GeoSource™ Ultra
®
Forced Air Horizontal Models
Performance Ratings
Ground Loop
Rated according to ISO 13256-1, which includes power consumption for water pumping.
HEATING
32°F EWT
Ground Loop
COOLING
77°F EWT
Ground Loop
MODEL
CFM
GPM
BTU/hr
COP
BTU/hr
EER
GH 170/171
625
5
14,700
3.3
17,400
14.1
GH/270/271
900
7
23,100
3.4
25,300
15.2
GH 370/371
1,100
8
32,800
3.3
35,400
14.1
GH 470/471
1,550
11
45,700
3.3
48,000
14.1
GH 570/571
1,800
13
54,800
3.3
58,000
14.1
GH 670/671
2,100
16
66,700
3.2
65,600
12.5
GH 870/871
2,700
22
78,500
3.3
88,000
14.1
GH 1100/
1101
1st Stage
2000
30
63,800
4.0
72,500
18.5
2nd Stage
3150
30
99,500
3.3
105,300
13.5
Ground Water
Rated according to ISO 13256-1, which includes power consumption for water pumping.
HEATING
50°F EWT
Ground Water
COOLING
59°F EWT
Ground Water
MODEL
CFM
GPM
BTU/hr
COP
BTU/hr
EER
GH 170/171
625
3
17,000
3.6
18,000
16.2
GH 270/271
900
4
24,800
3.7
26,900
16.4
GH 370/371
1,100
5
36,500
3.6
35,600
16.3
GH 470/471
1,550
7
51,500
3.6
50,100
16.2
GH 570/571
1,800
9
62,200
3.6
58,000
16.2
GH 670/671
2,100
12
76,500
3.5
70,200
15.0
GH 870/871
2,700
16
89,000
3.6
93,000
16.2
GH 1100/
1101
1st Stage
2,000
20
64,900
4.1
76,400
20.4
2nd Stage
3,150
20
115,500
3.5
113,600
16.0
(back to
Ultra Forced Air introduction
)
Home
|
Contact ECONAR
|
Site Map
©2010 ECONAR®, a brand of GeoSystems®, LLC
Disclaimer
Privacy Policy
1-800-4-ECONAR