Dealer Locator | Case Studies | About ECONAR | Contact Information | Home GeoSource™ Ultra® Hydronic Performance
Ratings
Ground Loop
AHRI/ISO 13256-2
|
HEATING
2nd Stage: 32 °F EWT
1st Stage: 41 °F EWT
|
COOLING
2nd Stage: 77°F EWT
1st Stage: 68°F EWT
|
|
104°F HYD EWT
|
53.6°F
HYD EWT
|
|
|
Hydronic
GPM |
Ground
GPM |
BTU/hr
|
COP
|
BTU/hr
|
EER
|
| GW/370/371 |
9
|
9
|
26,700
|
3.0
|
33,200
|
16.5
|
| GW/470/471 |
12
|
12
|
37,000
|
3.0
|
44,500
|
16.4
|
| GW/570/571 |
15
|
15
|
48,000
|
3.0
|
54,400
|
16.3
|
| GW/770/771 |
18
|
18
|
58,800
|
3.0
|
71,500 |
16.9
|
| GW/870/871 |
20 |
20 |
66,400 |
3.0 |
79,800 |
15.5 |
| |
GW/1100
/1101 |
1st Stage |
20 |
30 |
53,300 |
3.4 |
60,400 |
18.5 |
| 2nd Stage |
20 |
30 |
97,300 |
2.8 |
100,500 |
14.1 |
| GW/2400 |
1st Stage |
40 |
60 |
130,600 |
4.3 |
142,000 |
21.8 |
| 2nd Stage |
40 |
60 |
222,400 |
4.3 |
240,700 |
15.2 |
| GW/3600 |
1st Stage |
54 |
78 |
189,750 |
4.3 |
191,700 |
19.6 |
| 2nd Stage |
54 |
78 |
318,000 |
3.3 |
316,500 |
14.6 |
Ground Water
AHRI/ISO 13256-2 |
HEATING
50°F Grd EWT
|
COOLING
50°F Grd EWT |
104°F HYD EWT |
53.6°F HYD EWT |
|
Hydronic
GPM |
Ground
GPM |
BTU/hr |
COP |
BTU/hr |
EER |
| GW/370/371 |
9 |
9 |
33,300 |
3.5 |
35,900 |
21.5 |
| GW/470/471 |
12 |
12 |
43,500 |
3.5 |
46,900 |
20.4 |
| GW/570/571 |
15 |
15 |
58,900 |
3.5 |
61,800 |
20.4 |
| GW/770/771 |
18 |
18 |
73,800 |
3.5 |
74,300 |
21.3 |
| GW/870/871 |
20 |
20 |
82,800 |
3.5 |
83,800 |
19.2 |
| |
GW/1100
/1101 |
1st Stage |
20 |
20 |
53,300 |
3.8 |
62,350 |
22.2 |
| 2nd Stage |
20 |
20 |
105,300 |
3.2 |
108,700 |
18.0 |
|
|